Thursday, 30 July 2015

Site visit 24.07.15

 Framing underway to Bean link soffit trespa cladding

 CVA to check spec. for Cunliffe tiling adjacent water fountains as inconsistencies on site- 2FL + 1FL-POSTSCRIPT- 1st floor tiling to CU.01.05 wc lobby area incorret. Finish should be natural not Bocciardato- Action HCL
 Trespa lining underway to arcade. HCL to clean all panels on completion- Action HCL

BE.00.14- acoustic panel hanging- ceilings to all be made good where damage to soffit on installation- Action HCL
 BE.00.14 bulkhead- incorrect ceiling not removed and 2 further ceilings added- not as CVA detail BE 12.4
 Ceiling hatches to BE.00.14- problems with fitting due to location of tray above- HCL to advise

 BE.00.10 precast concrete column/ beam- to be made good/ redecorated as per previous comments regarding finish of concrete- Action HCL

 Bean stair BE.00.02- awaiting carpet/ nosings. New stair tile to corners as M10/ 116- HCL to advise

 Water ingress to  BE.EW.01.06. Screen awaiting capping. Plasterboard now damaged. Replace and make good decorations- Action HCL

 Ditto- water ingress to be addressed

 Sedum now installed to arcade roof

BE.RL.01.01- Interface to rooflight lantern linings- holes filled poorly/ inconsistent. HCL to address - Action HCL

 BE.RL.01.04- perforate plasterboard to ends- boards do not align/ edge bead required- Action HCL

  
Ditto

 BE.RL.01.01-lining not as CVA detail BE 12.5- lining to align vertically with window board and not extend to glazing. HCL to modify and set back nominal 50mm and apply edge bead to finish.- Action HCL


 BE.EW.01.08- lining completed internally but water ingress issue not addressed- DPC/ EDPM to be completed as CVA detail BE 15.3- Action HCL

 BE.EW.01.08- ceiling/ lining not completed as CVA detail BE 15.3- Action HCL

 New joinery stained/ damaged/ still unprotected- Action HCL
 Edge detail to MDF window reveals generally poor- HCL to make good surface/ decoration- Action HCL
 CU.ID.02.06- door catching/ marking tile

 Ditto MDF window reveals

 CU.ID.00.15- threshold/ level to be addressed- Action HCL

 Bean LRC overview

 Hit and miss brickwork above CU.ED.00.05 to be removed/ grille added/ support added/ brick rebuilt- Action HCL
 Bean 1FL interior overview

 RCP recess not as CVA detail BE 07.1- slot to be continuous. - Action HCL

Bean LRC link-ceiling airtight detail not as CVA details BE 18.2 or subsequent HCL sketch- Action HCL